Load isolation switch HGLZ1-100-4

HGL-160A/4Z2JF11~380V In 125A
· Transfer load isolation switch
· Left and right arrangement
· AC rated voltage 380V
· Contracted heating current 160A
· Rated current 125A
· 4 poles, outside cabinet operation, auxiliary contact
· 1 normally open +1 normally closed

Model and Meaning


Selection For

HGL-160A/4Z2JF11~380V In 125A

· Transfer load isolation switch

· Left and right arrangement

· AC rated voltage 380V

· Contracted heating current 160A

· Rated current 125A

· 4 poles, outside cabinet operation, auxiliary contact

· 1 normally open +1 normally closed

Normal Operating Conditions and Installation Conditions

1. The ambient air temperature should not be higher than +40 ° C or lower than -5 ° C, and the relative humidity should not be greater than 95%.

2. The altitude of the installation site should not exceed 2000 meters.

3. No explosive hazardous medium.

4. No rain or snow invades the environment.

Note: If intended to be used at ambient air temperature above +40℃ or below -5℃, the user should explain to the manufacturer.

Meet Criterion

International standard

IEC 60947-1 “low-voltage switching equipment and control equipment part I: General”

IEC 60947-3 “low-voltage switching equipment and control equipment, switches, isolators, isolation switch and fuse combination appliances”

National standard

GB/T 14048.1 “Low-voltage switchgear and control equipment general Provisions”

GB/T 14048.3 “Low-voltage switchgear control equipment, low-voltage switches, isolators, isolators and fuse combined appliances”

alien isolation switch

isolator switch on or off

HGL-63~3150A Load-Disconnector Switch

Alien Isolation Switch HGL series are designed for use in a variety of applications where circuit turn-on and turn-off or electrical isolation is required. They are available in seven different models, ranging from 63A to 3150A, and feature a modular design with three and four levels (three levels + neutral level for turn-on and turn-off).

Alien Isolation Switch is also equipped with a front-side window that indicates the contact’s on/off state, and a rear observation window that allows for direct observation of the contact’s on-off state.

Main Technical Parameters 

Rated current In (A)

63A

100A

160A

250A

630A

Contract heating current Ith (A) 

40

63

80

100

125

160

200

250

315

400

500

630

Rated insulation voltage Ui (V) (Installation class IV)

690

690

1000

1000

1000

Dielectric strength (V)

1890

1890

2200

2200

2200

Rated impulse withstand voltage Uimp kV

8

8

12

12

12

Rated operating current le (A) 

AC-21B

40

63

80

100

125

160

200

250

315

400

500

630

 

AC-22B

40

63

80

100

125

160

200

250

315

400

500

630

 

AC-23B

40

63

80

100

125

160

200

250

315

400

500

630

Motor power P (kW) 

400V

18.5

25

40

40

63

80

100

132

160

220

280

315

Rated short-time endurance current lcw (kA Rms) 1s

2

2

2

2

6

6

9

9

12.6

12.6

12.6

12.6

Rated breaking capacity Icn (A Rms) AC-23B 400V

320

504

640

800

1000

1080

1600

2000

2520

3200

4000

5040

Rated switching capacity Icm (A Rms) AC-23B 400V 

400

630

800

1000

1250

1600

2000

2500

3150

4000

5000

6300

Rated short-circuit switching capacity Icm (kA peak) 

2.84

2.84

2.84

2.84

9.2

9.2

15.3

15.3

25.2

25.2

25.2

25.2

Mechanical life 400V 

1700

1700

1700

1700

1400

1400

1400

1400

800

800

800

800

Electrical life 400V

300

300

300

300

200

200

200

200

200

200

200

200

Operating torque (Nm)

1.2

1.2

1.2

1.2

6.5

6.5

10

10

21

21

21

21

Weight (kg)

3P

0.4

0.4

0.55

0.55

1.2

1.2

2

2

4.4

4.4

4.9

4.9

 

4P

0.42

0.42

0.62

0.62

1.4

1.4

2.35

2.35

5.5

5.5

6.3

6.3



Rated current In (A)

1600A

3150A

Contract heating current Ith (A)

1000

1250

1600

2000

2500

3150

Rated insulation voltage Ui (V) (Installation class IV)

1000

1000

Dielectric strength (V)

2200

2200

Rated impulse withstand voltage Uimp kV

12

12

Rated operating current le (A)

AC-21B

1000

1250

1600

2000

2500

3150

AC-22B

/

/

/

/

/

/

AC-23B

/

/

/

/

/

/

Motor power P (kW)

400V

560

560

560

710

710

710

Rated short-time endurance current lcw (kA Rms) 1s

30

30

30

50

50

50

Rated breaking capacity Icn (A Rms) AC-23B 400V

1500

1875

2400

3000

3750

4725

Rated switching capacity Icm (A Rms) AC-23B 400V

1500

1875

2400

3000

3750

4725

Rated short-circuit switching capacity Icm (kA peak)

63

63

63

105

105

105

Mechanical life 400V

500

500

500

500

500

500

Electrical life 400V

100

100

100

100

100

100

Operating torque (Nm)

37

37

37

50

50

50

Weight (kg)

3P

13.2

14.6

15.6

25.5

25.5

31

4P

14.8

17.1

18

37.5

37.5

51.5

Operating Mode