Model and Meaning
Selection For
HGL-160A/4Z2JF11~380V In 125A
· Transfer load isolation switch
· Left and right arrangement
· AC rated voltage 380V
· Contracted heating current 160A
· Rated current 125A
· 4 poles, outside cabinet operation, auxiliary contact
· 1 normally open +1 normally closed
Normal Operating Conditions and Installation Conditions
1. The ambient air temperature should not be higher than +40 ° C or lower than -5 ° C, and the relative humidity should not be greater than 95%.
2. The altitude of the installation site should not exceed 2000 meters.
3. No explosive hazardous medium.
4. No rain or snow invades the environment.
Note: If intended to be used at ambient air temperature above +40℃ or below -5℃, the user should explain to the manufacturer.
Meet Criterion
International standard
IEC 60947-1 “low-voltage switching equipment and control equipment part I: General”
IEC 60947-3 “low-voltage switching equipment and control equipment, switches, isolators, isolation switch and fuse combination appliances”
National standard
GB/T 14048.1 “Low-voltage switchgear and control equipment general Provisions”
GB/T 14048.3 “Low-voltage switchgear control equipment, low-voltage switches, isolators, isolators and fuse combined appliances”
alien isolation switch
isolator switch on or off
HGL-63~3150A Load-Disconnector Switch
Alien Isolation Switch HGL series are designed for use in a variety of applications where circuit turn-on and turn-off or electrical isolation is required. They are available in seven different models, ranging from 63A to 3150A, and feature a modular design with three and four levels (three levels + neutral level for turn-on and turn-off).
Alien Isolation Switch is also equipped with a front-side window that indicates the contact’s on/off state, and a rear observation window that allows for direct observation of the contact’s on-off state.
Main Technical Parameters
Rated current In (A) |
63A |
100A |
160A |
250A |
630A |
||||||||
Contract heating current Ith (A) |
40 |
63 |
80 |
100 |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
Rated insulation voltage Ui (V) (Installation class IV) |
690 |
690 |
1000 |
1000 |
1000 |
||||||||
Dielectric strength (V) |
1890 |
1890 |
2200 |
2200 |
2200 |
||||||||
Rated impulse withstand voltage Uimp kV |
8 |
8 |
12 |
12 |
12 |
||||||||
Rated operating current le (A) |
AC-21B |
40 |
63 |
80 |
100 |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
AC-22B |
40 |
63 |
80 |
100 |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
|
AC-23B |
40 |
63 |
80 |
100 |
125 |
160 |
200 |
250 |
315 |
400 |
500 |
630 |
Motor power P (kW) |
400V |
18.5 |
25 |
40 |
40 |
63 |
80 |
100 |
132 |
160 |
220 |
280 |
315 |
Rated short-time endurance current lcw (kA Rms) 1s |
2 |
2 |
2 |
2 |
6 |
6 |
9 |
9 |
12.6 |
12.6 |
12.6 |
12.6 |
|
Rated breaking capacity Icn (A Rms) AC-23B 400V |
320 |
504 |
640 |
800 |
1000 |
1080 |
1600 |
2000 |
2520 |
3200 |
4000 |
5040 |
|
Rated switching capacity Icm (A Rms) AC-23B 400V |
400 |
630 |
800 |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
4000 |
5000 |
6300 |
|
Rated short-circuit switching capacity Icm (kA peak) |
2.84 |
2.84 |
2.84 |
2.84 |
9.2 |
9.2 |
15.3 |
15.3 |
25.2 |
25.2 |
25.2 |
25.2 |
|
Mechanical life 400V |
1700 |
1700 |
1700 |
1700 |
1400 |
1400 |
1400 |
1400 |
800 |
800 |
800 |
800 |
|
Electrical life 400V |
300 |
300 |
300 |
300 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
200 |
|
Operating torque (Nm) |
1.2 |
1.2 |
1.2 |
1.2 |
6.5 |
6.5 |
10 |
10 |
21 |
21 |
21 |
21 |
|
Weight (kg) |
3P |
0.4 |
0.4 |
0.55 |
0.55 |
1.2 |
1.2 |
2 |
2 |
4.4 |
4.4 |
4.9 |
4.9 |
|
4P |
0.42 |
0.42 |
0.62 |
0.62 |
1.4 |
1.4 |
2.35 |
2.35 |
5.5 |
5.5 |
6.3 |
6.3 |
Rated current In (A) |
1600A |
3150A |
|||||
Contract heating current Ith (A) |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
|
Rated insulation voltage Ui (V) (Installation class IV) |
1000 |
1000 |
|||||
Dielectric strength (V) |
2200 |
2200 |
|||||
Rated impulse withstand voltage Uimp kV |
12 |
12 |
|||||
Rated operating current le (A) |
AC-21B |
1000 |
1250 |
1600 |
2000 |
2500 |
3150 |
AC-22B |
/ |
/ |
/ |
/ |
/ |
/ |
|
AC-23B |
/ |
/ |
/ |
/ |
/ |
/ |
|
Motor power P (kW) |
400V |
560 |
560 |
560 |
710 |
710 |
710 |
Rated short-time endurance current lcw (kA Rms) 1s |
30 |
30 |
30 |
50 |
50 |
50 |
|
Rated breaking capacity Icn (A Rms) AC-23B 400V |
1500 |
1875 |
2400 |
3000 |
3750 |
4725 |
|
Rated switching capacity Icm (A Rms) AC-23B 400V |
1500 |
1875 |
2400 |
3000 |
3750 |
4725 |
|
Rated short-circuit switching capacity Icm (kA peak) |
63 |
63 |
63 |
105 |
105 |
105 |
|
Mechanical life 400V |
500 |
500 |
500 |
500 |
500 |
500 |
|
Electrical life 400V |
100 |
100 |
100 |
100 |
100 |
100 |
|
Operating torque (Nm) |
37 |
37 |
37 |
50 |
50 |
50 |
|
Weight (kg) |
3P |
13.2 |
14.6 |
15.6 |
25.5 |
25.5 |
31 |
4P |
14.8 |
17.1 |
18 |
37.5 |
37.5 |
51.5 |
Operating Mode